The start-up detector is matched with the automatic tracking and positioning jet fire extinguishing device (high-flow nozzle) of model ZDMP0.25/5S-YKS6.
Up to 4 high-flow nozzles can be controlled.
Dual-band red and ultraviolet detection can detect fire sources at an early stage, with a rapid response and an extremely low false alarm rate.
It adopts single-chip microcomputer control technology, with strong anti-interference ability and stable and reliable operation.
It has communication functions, facilitating remote monitoring.
The sensitivity can be set on site.
| Product model | HZD-YKS-2 |
| Working voltage | DC12V |
| Power consumption | ≤ 1W |
| Installation height | 6~15m |
| Detection radius | ≤ 12m |
| Response time | ≤ 30s |
| Working temperature | 4℃ ~55℃ |
| External dimensions | Φ128mm×50mm |