It operates in a networked manner with the electrical fire monitoring equipment produced by our company.
There are 5 channels of residual current detection and 5 channels of temperature detection (corresponding to 10 network addresses).
It has the function of monitoring faults in sensor circuits;
Use an AC220V power supply.
| Product model | DH-YKS4943 |
| Working voltage | AC220V +10% 50Hz AC220V -15% 50Hz |
| Working current | ≤ 10mA(AC220V/50Hz) |
| Set the alarm current | 300mA~990mA(Step 10mA) |
| Set the alarm temperature | 55℃~140℃(Step 1℃) |
| The number of channels and detection range | Five residual currents(0~999mA) |
| 5-channel temperature | 25℃ ~ 140℃ |
| Bus address range | 1-127 |
| External dimensions | 160mm×99mm×45mm |
| Material | ABS |
| Installation method | There are multiple installation methods, including track installation, wall-mounted installation, and panel embedded installation |
| Enforce standards | Optional GB14287-2014 Electrical Fire Monitoring System |