Chinese

Automatic fire alarm system

Combustible gas alarm controller

Product Features

Comply with GB16808-2008 combustible gas alarm controller;

TFT color liquid crystal display

Reserve interfaces such as USB external CAN, internal CAN, RS485, RS232, and loop.

Multiple communication methods such as external CAN bus, internal CAN bus, and loop bus.

Product Parameters

Product model JB-KR-YKS4891
Working voltage The main power supply is AC220V and the backup power supply is DC12V. Two batteries are connected in series
Working current (monitoring, alarm) Monitoring/alarm ≤ 10W
Working temperature 0℃ ~40℃
Relative humidity ≤ 95%
Whole machine capacity There are 2 circuits, each with 127 address points
Structural form Wall-mounted
External dimensions 600mm×440mm×120mm
Linear requirements Power supply ZR-BV2×2.5, signal RVS2×1.5
Transmission distance RS485<1500m、CAN<2000m、Loop <2000m(Depending on the number of loads)