Automatic fire alarm system

Input/output module

Product Features

Two-bus, non-polar

Electronic coding method, occupying one address point;

It can provide DC passive normally open contact signals or point motion signals without the need for DC24V.

Receive passive feedback signals from controlled devices;

It has the function of line fault detection and selection, and monitors the open circuit fault of switch signals.

Product Parameters

Product model JKM-YKS4210C
Working voltage DC18~24V
Working current ≤ 450uA
Coding method Electronic coding
Wiring method The two-wire bus is non-polar
Output contact Passive contact signal capacity: 30VDC/2A,125VAC/1A
Control mode Continuous or intermittent output
Working environment Temperature :-10℃ to 55℃ Relative humidity: ≤ 92%(at 40℃)
External dimensions 100mm×82mm×34mm
Material ABS resin